Rack power calculator

Enter what each device draws and how many there are. The calculator adds them up in watts and amps at 230 V and sets the total against your PDU or breaker rating and the continuous-load limit.

Devices on one PDU or breaker

Filled in with example numbers. Change any of them.

Total

The figures appear here when the page has loaded.

Estimates only, from the numbers you enter. Single-phase 230 V. Electrical load only: cooling is not included.

Check the whole room

One rack can look fine on its own and still trip when a feed goes off and its load moves to the other PDU. The full tool works that out across the room. The devices typed here go with it on a PDU, one per unit (one per row past 800 units), for the cords and outlets to be added there. The room open in the tool is kept, unless it came from here unchanged. Its "Bring back the last room" button restores it. Only one earlier room is kept.

How the amps are worked out

Amps are watts divided by 230 times the power factor, the same sum the full tool uses. The power factor starts at 0.95, the tool's default; change it if the device label gives another. Watts on a label are often a maximum rather than what the device draws, so a measured figure is better where there is one.

The 80 % line

Many guides suggest keeping a continuous load below 80 % of a breaker's rating. The calculator starts its limit at 80 % and says which side of it the total is on. It is a setting, not a rule from a standard, and it can be changed. A load exactly at the rating is not counted as over it; only a load above it is.

One rack is not the whole room

With two PDUs on two feeds, each one normally carries part of the load. When a feed goes off, the other PDU takes all of it. The full tool adds each rack's load to the PDU and bank that would take it over, and shows which devices go dark and which bank is assumed to trip.

What it leaves out

Cooling, start-up surges and three-phase supplies are not part of this sum. Banks within a PDU are not either: a bank behind a smaller breaker can trip before the PDU does, which the full tool shows device by device.

Questions

Does it include cooling?

No. It is electrical load only.

Why amps and not kilowatts?

PDUs and breakers are rated in amps, so amps are what the load is compared with.

Does it handle three-phase?

Not in this version. Everything here is single-phase 230 V.

Where does a device's draw come from?

On its label, in the maker's data sheet, or from a meter. The full tool has a library of label figures for many models, which may be wrong or missing.

Is the answer a guarantee?

No. It is an estimate worked out from the numbers entered.